Header Size Calculator

The size of a load-bearing header is a table lookup, not a guess. This tool sizes built-up and single-member wood headers straight from IRC 2021 Tables R602.7(1), R602.7(2), and R602.7(3) — by building width, ground snow, and what the header supports — and tells you the jack studs and full-height studs required at each end.

IRC 2021 prescriptive sizing — Tables R602.7(1)/(2)/(3). No. 2 Douglas fir-larch, hem-fir, Southern pine, or SPF. Engineered lumber (LVL/PSL) uses its own manufacturer tables.
Measured perpendicular to the ridge. Interpolation is permitted between the 12 / 24 / 36-ft columns.
≤30 uses the 30 psf column (roof live ≤ 20 psf); 30–50 may be interpolated; above 50 the 70 psf column is used (conservative).
Center-bearing = floor joists bear on a center girder; clear-span = joists cross the full width with no intermediate support.
Clear span between the jack studs — use the rough opening width for a door or window.
Built-up = two (or more) 2× members nailed together. Single-member = flat 2× with wall plates top and bottom per R602.7.1 — a less common detail.
Picks the Table R602.7.5 column for full-height studs at each header end.
The tables assume the header top is braced. Where cripple studs bear directly on the header with nothing bracing it sideways, spans for 2×8 / 2×10 / 2×12 headers are limited to 70% of the tabulated span (table footnote) — this calculator applies that factor when you uncheck this box.
Header size2-2×6
Max span at your parameters4-07 (24-ft width)
Jack studs, each end1 (or approved framing anchor)
Full-height studs, each end1
Code basisR602.7(1) · Roof + ceiling · 24-ft width · ≤30 psf column

Spans are maximums: the smallest header that reaches your opening is selected. Table assumes No. 2 lumber of DF-L / hem-fir / Southern pine / SPF and 2-ply built-up framing (2× members nailed together) — verify local amendments and the actual lumber grade before framing.

What a header does

A header is the horizontal member that spans an opening in a bearing wall — a door, a window, a garage door. Everything the wall above used to carry now rides on it: roof and ceiling framing in an exterior wall, floor loads as well in interior and multi-story cases. The load has to travel around the opening, not through it.

The path is short. Roof and floor framing lands on the top plate, cripples carry it down to the top of the header, the header carries it across the opening, and jack studs carry each end down to the sole plate. That is why each table cell gives two things — a header size and a jack-stud count, the NJ column.

The studs around an opening are not interchangeable:

Jack studs and cripples are not optional: the header needs the first, the top plate needs the second.

Reading the IRC R602.7 tables

Three tables cover prescriptive wood headers for No. 2 Douglas fir-larch, hem-fir, Southern pine, or SPF:

Interpolation is where people go wrong. The footnotes allow it in three places only: between the 12 / 24 / 36-ft width columns, between 30 and 50 psf ground snow, and between porch depths of 8 and 14 ft. Everything else is a hard lookup — spans are never interpolated between sizes, and above 50 psf the table sends you to the 70 psf column rather than interpolating. Nothing here reaches past 36 ft of width, 70 psf, or two floors — beyond that it is an engineered design.

The 0.70 lateral-bracing reduction

Every span assumes the top of the header is braced sideways by perpendicular framing — joists or rafters crossing over it. Where cripples bear directly on the header with nothing bracing it, the footnote limits 2×8, 2×10, and 2×12 header spans to 70% of the tabulated value.

That is not a small haircut. A 2-2×10 spans 6-10 (82 in) at a 24-ft building width and 30 psf when braced, but only 82 × 0.70 = 57.4 in unbraced — which does not cover a 6-ft opening. It is the difference between a header that passes inspection and one that does not, decided by how you stack the wall rather than the lumber you bought.

Built-up headers vs single-member headers

A built-up header is two or more 2× members nailed together on edge — the 2-ply 2×10 or 2×12 over most sliding-door and garage openings. Table R602.7(1) also prints single-member rows, 1-2×6 through 1-2×12, which R602.7.1 permits only with a specific detail: a single flat 2× member, or a wall plate, not less in width than the studs, at the top and bottom of the header, face-nailed with 10d box nails (3″ × 0.128″) at 12″ on center.

The single-member route is not a shortcut. At a 24-ft width, 30 psf, roof and ceiling only: a single 1-2×12 spans 5-5 (65 in) with 2 jack studs each end, while a built-up 2-2×8 spans 5-9 (69 in) with 1 — the built-up header out-spans the single member and needs less end support.

Worked example — 6-ft opening, exterior wall

A 6-ft 0-in opening — a 72-in clear opening — in an exterior bearing wall of a 24-ft-wide building, 30 psf ground snow, roof and ceiling only, built-up header with the top braced. Walk the built-up rows at 24-ft width and 30 psf:

2-2×10, 2 jack studs each end. The span you found is a maximum, not a target. Two things move that answer:

Full-height studs are a separate count. Table R602.7.5 sets the minimum at each end of an exterior header from the header span: 1 stud for a span of 4 through 8 ft under the typical ≤115 mph Exposure B column, 2 from 10 ft up, and 2 to 4 studs under the higher wind column (less than 140 mph Exposure B / less than 130 mph Exposure C).

Common mistakes

Header size FAQ

What size header do I need for a door or window opening?

Read Table R602.7(1) for an exterior bearing wall: pick your building width column (12 / 24 / 36 ft, interpolating between them) and ground snow (30 / 50 / 70 psf), find the row for what the header supports, then take the smallest header whose maximum span covers your clear opening. Each cell also gives the jack studs required at each end.

Does ground snow load change the header size?

Yes. At a 24-ft building width with roof and ceiling above, a 2-2×10 spans 6-10 (82 in) at 30 psf but only 5-11 (71 in) at 50 psf, so a 6-ft opening that took a 2-2×10 becomes a 2-2×12.

What is the 0.70 lateral-bracing factor for headers?

The tables assume the top of the header is braced by perpendicular framing above it. Where cripples bear directly on the header with nothing bracing it, the footnote limits 2×8, 2×10, and 2×12 header spans to 70% of the tabulated value.

What is the difference between a built-up and a single-member header?

A built-up header is two or more 2× members nailed together on edge — the usual 2-ply header. A single-member header is one flat 2× member or wall plate, permitted by R602.7.1 only where a plate not less in width than the studs runs at the top and bottom of the header, face-nailed with 10d box nails (3″ × 0.128″) at 12″ on center.