What Size Wire for a 200 Amp Service?

"200 amp wire" is really two different questions. A service supplying the whole house is allowed to use a smaller conductor than a 200 A feeder that supplies only part of it. Same breaker, different code rule, different answer.

The short answer

It depends on what the 200 A breaker is protecting, and the code treats the two cases very differently:

Minimum 200 A conductor by application (NEC Table 310.16 at 75°C, with the 310.12 allowance for a whole-dwelling service)
ApplicationCopperAluminium
200 A service, or a feeder carrying the entire load of the dwelling2/0 AWG — 175 A (83% rule)4/0 AWG — 180 A (83% rule)
200 A subpanel feeder, or any feeder not carrying the whole dwelling load3/0 AWG — 200 A250 kcmil — 205 A

If that looks like two sizes too many for one question, that is the point. The lower row is the conservative answer that is always legal. The upper row is a genuine code allowance that applies to exactly one case — a service (or feeder) that supplies the entire load of a one-family dwelling — and gets misapplied constantly when someone reads it off a chart for a garage subpanel.

Why there are two answers: the 83% rule

NEC 310.12 (it was 310.15(B)(7) before the 2023 code renumbered it) says that for a service or feeder rated 100 through 400 A, the conductors supplying the entire load of a dwelling shall be permitted to have an ampacity not less than 83 percent of the service rating. The reasoning is diversification: a dwelling's connected load is a set of appliances that do not all run at once, so the service conductors do not need to carry the full rating continuously.

For a 200 A service, the arithmetic is 200 A × 0.83 = 166 A. So the conductor only needs an ampacity of 166 A, not 200 A. Reading Table 310.16 at 75°C, 2/0 copper is 175 A and 4/0 aluminium is 180 A — the two smallest sizes that clear 166 A. That is where the widely repeated "2/0 copper or 4/0 aluminium for 200 A" answer comes from, and it is correct for a service.

The code also publishes this as a lookup table, Table 310.12, so you do not have to run the 83% multiplication yourself. Its 200 A row reads 2/0 copper and 4/0 aluminium. Two conditions matter: the table is for a 120/240 V, single-phase system, and it may only be used where no ampacity adjustment or correction factors are required (310.12(A) and (B)). If the conductors are bundled with others or run through a hot space, do the derating first and the 83% shortcut is off the table.

Why a subpanel gets the bigger wire

310.12 reaches a conductor only when it supplies the entire load of the dwelling. A subpanel in a garage, a shop, or a second floor supplies part of the load, downstream of the main. The whole-load condition is not met, so the allowance is not available and full ampacity applies: a 200 A breaker needs a conductor rated at least 200 A. That means 3/0 AWG copper (200 A at 75°C) or 250 kcmil aluminium (205 A at 75°C).

240.4(B) does not rescue the smaller size here, and the reason is subtle. That rule lets a conductor sit on the next higher standard device where its ampacity does not match a standard rating. 2/0 copper is 175 A — and 175 A is a standard rating in 240.6(A). Because the ampacity already corresponds to a standard device, there is nothing to round up to, so 2/0 copper stays on a 175 A breaker. (Compare 4 AWG copper at 85 A, where 85 A is not a standard rating and 240.4(B) does let it reach a 90 A device.) The full standard-rating list is on the breaker size chart.

Which temperature column?

For a 200 A circuit the answer is the 75°C column. NEC 110.14(C)(1)(b) directs conductors for circuits rated over 100 A to the 75°C ampacity unless the equipment is listed and identified for a higher rating. Almost all modern panelboards and breakers are rated 75°C, so 2/0 copper (175 A), 3/0 copper (200 A) and 250 kcmil aluminium (205 A) are read from that column. The 60°C column that decides the small-conductor feeder questions never comes into play at 200 A, which is one fewer trap than the sub-100 A case.

The rule of thumb that survives contact with the code: if the 200 A breaker feeds the whole house, the 83% rule applies and 2/0 copper or 4/0 aluminium is allowed. If it feeds anything smaller than the whole house, it does not, and you need 3/0 copper or 250 kcmil aluminium. Then check voltage drop, and size for the larger of the two.

Distance: holding a 3% drop

Ampacity sets the floor; distance sets the reality. The formula this site's voltage drop calculator uses is Vd = 2 × L × I × R ÷ 1,000 for single-phase, one-way length in feet, R from NEC Chapter 9 Table 8 (75°C, uncoated, ohms per 1,000 ft). On a 240 V system, 3% is 7.2 V. Strictly, the 3% and 5% figures are informational notes to 210.19(A)(1) and 215.2(A)(1), not enforceable rules — 90.5(C) says notes are not binding. In practice a long feeder to a shop is exactly where the note earns its keep.

Here is what the arithmetic gives for a feeder carrying the full 200 A, starting from the ampacity minimum in each material (Table 8 resistances: 3/0 Cu 0.0766, 4/0 Cu 0.0608, 250 kcmil Al 0.0847, 300 kcmil Al 0.0707 Ω per 1,000 ft):

200 A feeder on a 240 V single-phase run — smallest conductor holding 3% voltage drop
One-way runCopperAluminium
100 ft3/0 Cu — 3.06 V, 1.3%250 kcmil Al — 3.39 V, 1.4%
150 ft3/0 Cu — 4.60 V, 1.9%250 kcmil Al — 5.08 V, 2.1%
200 ft3/0 Cu — 6.13 V, 2.6%250 kcmil Al — 6.78 V, 2.8%
250 ft4/0 Cu — 6.08 V, 2.5%300 kcmil Al — 7.07 V, 2.9%

Both materials hold the ampacity minimum through 200 ft and step up once at 250 ft. Copper climbs from 3/0 to 4/0; aluminium from 250 kcmil to 300 kcmil. The failing steps that force the bump are 3/0 Cu at 250 ft = 2 × 250 × 200 × 0.0766 ÷ 1,000 = 7.66 V (3.19%, over the line) and 250 kcmil Al at 250 ft = 2 × 250 × 200 × 0.0847 ÷ 1,000 = 8.47 V (3.53%).

Note that the service case starts from a smaller ampacity minimum — 2/0 copper or 4/0 aluminium — but voltage drop reimposes a floor once the run is long. On 2/0 copper at 200 A, 150 ft drops 5.80 V (2.42%) and 200 ft drops 7.74 V (3.22%) — so a 200 ft service run on the 83% conductor has to come back up to 3/0 copper anyway. The two answers converge as distance grows.

Worked example — 200 ft to a detached shop

A 200 A subpanel in a detached shop, 200 ft from the house panel, 240 V single-phase, and you intend to use the full 200 A eventually. This is a subpanel, not a whole-house service, so the 83% rule is off the table.

Step 1 — ampacity. A 200 A breaker needs a conductor rated at least 200 A. At 75°C that is 3/0 AWG copper (200 A) or 250 kcmil aluminium (205 A). That is the floor.

Step 2 — voltage drop on 3/0 copper. Vd = 2 × 200 × 200 × 0.0766 ÷ 1,000. In pieces: 2 × 200 = 400 ft of conductor; 400 ÷ 1,000 = 0.4; 0.4 × 0.0766 = 0.03064 Ω of loop resistance; 0.03064 × 200 A = 6.13 V. As a percentage, 6.13 ÷ 240 × 100 = 2.55% — inside the 3% target. 3/0 copper works at 200 ft. In aluminium, 250 kcmil gives 0.4 × 0.0847 = 0.0339 Ω, × 200 A = 6.78 V = 2.82%, also inside.

Now push the same load to 250 ft and the picture changes. On 3/0 copper: loop resistance 2 × 250 × 0.0766 ÷ 1,000 = 0.0383 Ω, × 200 A = 7.66 V = 3.19% — just over. One size up, 4/0 copper is 0.0304 Ω × 200 A = 6.08 V = 2.53%, and it carries 230 A at 75°C. In aluminium, 250 kcmil at 250 ft = 8.47 V (3.53%), stepping to 300 kcmil at 7.07 V (2.95%). At 250 ft the honest answer is 4/0 copper or 300 kcmil aluminium.

The cost of getting this wrong is real but easy to overstate. At a genuine 200 A, 3/0 copper over 250 ft burns 200² × 0.0383 = 1,532 W as heat inside the run; 4/0 cuts that to 1,216 W. But note the assumption — 200 A continuous is worst case. If your Article 220 calculation says the real load is 120 A, then 3/0 copper at 250 ft drops 2 × 250 × 120 × 0.0766 ÷ 1,000 = 4.60 V, or 1.92%, and 3/0 is perfectly adequate. Size the voltage drop to the calculated load, not to the breaker handle.

Copper or aluminium?

Aluminium is about 1.6× the resistance of copper at the same size, so it needs to be two sizes larger for the same job — the table shows 250 kcmil aluminium doing the work of 3/0 copper. It is also markedly cheaper, which is why most 200 A service entrance conductors and long feeder runs are aluminium. The old reputation for loose connections is a termination problem, not a wire problem: the lugs must be listed for aluminium (AL/CU), the conductor stripped clean and torqued to the manufacturer's spec, and anti-oxidant compound applied where the connector requires it. Done correctly, aluminium is a legitimate, code-compliant choice. Copper is smaller and stiffer and easier to terminate in tight gutters, which is why some electricians still prefer it, particularly inside a crowded panel.

Don't forget the ground wire

The equipment grounding conductor for a 200 A feeder is sized from the rating of the overcurrent device, not from the phase conductors, per NEC Table 250.122: for a 200 A breaker that is a minimum 6 AWG copper or 4 AWG aluminium. Sizing it to match the hots is a common and pointless oversize.

A service is a different conductor again. The wire from the service disconnect to the ground rods is the grounding electrode conductor, sized from the service conductors per NEC Table 250.66, with a separate small-conductor exception for a rod-only connection. Mixing up Table 250.122 and Table 250.66 is one of the most common errors on service work.

If the subpanel is in a separate building, two more rules apply. NEC 250.32(A) requires the separate structure to have its own grounding electrode system — ground rods — connected to the feeder's equipment ground. And the subpanel keeps its neutral and equipment ground on separate bars: the main bonding jumper or bonding screw stays out, so the neutral is grounded at one point only, back at the service. The feeder is four wires — two hots, a neutral, and a separate equipment ground. The old three-wire arrangement survives only as a narrow exception for existing installations under 250.32(B); it is not something to design a new 200 A run around.

Common mistakes

Run your own numbers — the voltage drop and wire size calculator walks Table 8 for your distance, load, voltage and material, and applies the Table 310.16 ampacity floor and the 240.4(D) small-conductor caps on top, so it will not hand you a size the breaker cannot legally protect. Pair it with the NEC Table 310.16 ampacity chart to see every size and column at once.

200 amp service wire size FAQ

What size wire do I need for a 200 amp service?

For a 200 A single-phase residential service, NEC 310.12 permits 2/0 AWG copper or 4/0 AWG aluminium. The rule allows service conductors to have an ampacity of not less than 83% of the rating, so the floor is 200 x 0.83 = 166 A. At 75°C, 2/0 copper is 175 A and 4/0 aluminium is 180 A — both clear 166 A. Table 310.12 only applies where no ampacity adjustment or correction factors are required.

What size wire for a 200 amp subpanel?

A 200 A subpanel feeder needs the full 200 A, so it takes 3/0 AWG copper (200 A at 75°C) or 250 kcmil aluminium (205 A at 75°C) per NEC Table 310.16. The 83% rule in 310.12 does not apply, because a subpanel supplies only part of the dwelling's load, not the entire load.

Can I use 2/0 copper for a 200 amp subpanel?

No. 2/0 copper is 175 A at 75°C, and 175 A is itself a standard device rating in 240.6(A), so 240.4(B) cannot round it up to the next standard size. That is the difference from a size like 4 AWG (85 A), where the next standard rating — 90 A — is reachable. 2/0 copper belongs on a 175 A device, not a 200 A one.

How far can I run a 200 amp feeder before upsizing?

On a full 200 A load at 240 V, 3/0 copper holds a 3% drop (7.2 V) out to about 230 ft; 250 kcmil aluminium to about 212 ft. Past that, step up to 4/0 copper or 300 kcmil aluminium. If the real calculated load is lower than 200 A, the wire can be smaller and shorter — size the drop to the Article 220 load, not the breaker handle.

What size ground wire for a 200 amp service or subpanel?

They are different conductors. A 200 A subpanel feeder's equipment grounding conductor is sized from the breaker rating — 6 AWG copper or 4 AWG aluminium per NEC Table 250.122. A 200 A service's grounding electrode conductor (the wire to the ground rods) is sized from the service conductors per NEC Table 250.66, and is a separate calculation. A subpanel in a detached building also needs its own grounding electrode system under 250.32(A).

Related pages

Code references are to the 2023 NEC (NFPA 70) unless noted. Table 310.12 and Table 250.122 were re-checked 2026-10-05 against two independent reproductions; Table 8 resistances and Table 310.16 ampacities are the set verified 2026-09-16. Adopted editions and local amendments vary — this page is a working reference, not a substitute for a licensed electrician or your AHJ. No load calculation is performed for you.