Wire Ampacity Chart — NEC Table 310.16

The full allowable-ampacity table for copper and aluminium conductors, 60°C / 75°C / 90°C, 14 AWG through 2000 kcmil — plus the 240.4(D) small-conductor caps, the ambient-temperature correction factors, and the bundle adjustment that decides whether the size you picked is actually legal on your circuit.

The current the circuit must carry
Aluminium is not listed for 14 AWG
You may not beat the weakest termination
310.15(B)(1)(1) correction factor
310.15(C)(1) adjustment for bundled conductors
Minimum conductor size6 AWG Cu
Allowed ampacity at 6 AWG (60°C)55 A
Table 310.16 value, 60°C column55 A
Headroom on the load10%
Derating appliednone — base table conditions

Size ladder — allowed ampacity at each size:

SizeTableAllowedCap
6 AWG55 A55 A—
4 AWG70 A70 A—
3 AWG85 A85 A—
2 AWG95 A95 A—
1 AWG110 A110 A—
1/0 AWG125 A125 A—

Ampacity only. It answers "is this conductor legal to protect with this device?" — not "will the load at the far end get enough volts?" For runs over roughly 100 ft, check voltage drop as well and size for the larger of the two answers. Ampacities are NEC Table 310.16 for three or fewer current-carrying conductors at 30°C ambient; correction factors are Table 310.15(B)(1)(1) and 310.15(C)(1), verified 2026-09-25.

What ampacity is, and what it is not

Ampacity is the current a conductor can carry continuously without its insulation exceeding the temperature it is rated for. It is a safety limit, not a performance target: a conductor running at its ampacity is not "working hard", it is at the edge of how hot its insulation is allowed to get. Every number on this page describes a thermal limit, which is why the answer changes when the ambient temperature changes or when conductors are bundled together and cannot shed heat.

What ampacity does not tell you is whether the load at the far end will get enough voltage. A 10 AWG copper conductor carrying 30 A over 250 ft is perfectly legal on ampacity and will leave a 120 V load seeing about 106 V — a different failure with a different fix. Ampacity decides whether a conductor is legal; voltage drop decides whether it works. You size for the larger of the two.

Which of the three columns is legal on your job

Table 310.16 answers with three columns because conductor insulation comes in three temperature ratings. TW and UF are 60°C conductors. THWN, THHW, RHW and XHHW are 75°C. THHN, THWN-2, RHW-2, XHHW-2 and USE-2 are 90°C. A 90°C conductor is not automatically a licence to use the 90°C column, because the conductor is only one part of the circuit.

NEC 110.14(C) is the rule that governs the column. The ampacity you may use is limited by the lowest temperature rating of any termination, conductor or device in the circuit. For circuits of 100 A or less the ampacity is based on the 60°C column unless the equipment is listed and identified for use at 75°C — and most breakers, receptacles, switches and wire connectors are not listed for 90°C. That is why the practical answer for a residential circuit is the 60°C or 75°C column, and why "8 gauge is good for 55 amps" (the 90°C cell) is a statement about the wire, not about your circuit.

The rule in one line: derate from the column your conductor is rated for, then cap the result at the column your terminations are rated for. The lookup on this page takes the conservative path and derates from the termination column, so its answer is never smaller than the circuit really needs.

NEC Table 310.16 — full wire ampacity chart

Allowable ampacities of insulated conductors rated up to 2000 V, not more than three current-carrying conductors in a raceway, cable or earth (directly buried), based on an ambient temperature of 30°C (86°F). Values in amperes. 14 AWG aluminium is not listed.

NEC Table 310.16 — allowable ampacity (A), three or fewer current-carrying conductors, 30°C ambient
SizeCu 60°CCu 75°CCu 90°CAl 60°CAl 75°CAl 90°C
14 AWG152025———
12 AWG202530152025
10 AWG303540253035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115657585
2 AWG951151307590100
1 AWG11013014585100115
1/0 AWG125150170100120135
2/0 AWG145175195115135150
3/0 AWG165200225130155175
4/0 AWG195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350
600 kcmil350420475285340385
700 kcmil385460520315375425
750 kcmil400475535320385435
800 kcmil410490555330395445
900 kcmil435520585355425480
1000 kcmil455545615375445500
1250 kcmil495590665405485545
1500 kcmil525625705435520585
1750 kcmil545650735455545615
2000 kcmil555665750470560630

Three things are worth reading off that chart before you use it. First, doubling the cross-sectional area roughly doubles the ampacity: 12 AWG copper (20 A at 60°C) to 6 AWG (55 A) is a factor of 2.75 across five sizes. Second, aluminium sits about two sizes below copper — 2 AWG aluminium at 75°C is 90 A, between 4 AWG copper (85 A) and 3 AWG copper (100 A). Third, the 90°C column is much wider than the 60°C column at the same size — 12 AWG copper is 20 A at 60°C and 30 A at 90°C, a 50% difference. Almost every "the internet says this wire handles this many amps" argument is two people reading two different columns of this one table.

240.4(D) — the small-conductor caps that override the table

For 14, 12 and 10 AWG copper, and 12 and 10 AWG aluminium, the overcurrent device may not exceed the values below — regardless of what the 75°C or 90°C column says, and with no next-size-up allowance. The cap applies after any ambient-temperature and conductor-count correction factors have been applied, which is what makes a hot attic hard on small conductors.

NEC 240.4(D) — maximum overcurrent protection for small conductors
SizeCopper (A)Aluminium (A)
14 AWG15not listed
12 AWG2015
10 AWG3025

This is why a 20 A breaker on 12 AWG copper is the standard residential 20 A circuit, and why 14 AWG copper cannot be put on a 20 A breaker no matter how short the run — the cap is about the overcurrent device, not the load. Note that these are ceilings, not floors: they say how large a device may protect the conductor, not that the conductor can carry that much current in every environment.

The other half of that pairing — which device rating to round up to, and how the continuous-load rule and the 240.4(B) next-size-up change the answer — is worked through on the breaker size chart, including the per-appliance rows for water heaters, dryers, ranges and air conditioners.

How many amps can 12-gauge wire handle?

12 AWG copper is 20 A at 60°C, 25 A at 75°C and 30 A at 90°C in Table 310.16. 12 AWG aluminium is 15 A, 20 A and 25 A in the same three columns. Those are the raw table values — the number you may actually build to is set by two more rules, and together they are why 12 AWG copper is the standard 20 A circuit wire.

12 AWG ampacity by column, with the 240.4(D) overcurrent cap that applies on top
Conductor60°C75°C90°C240.4(D) cap
12 AWG copper20 A25 A30 A20 A
12 AWG aluminium15 A20 A25 A15 A

Read the two rules in order. First 110.14(C) fixes the column: on a circuit of 100 A or less the ampacity is taken from the 60°C column unless every termination, conductor and device is listed for 75°C, so a typical 12 AWG copper circuit is a 20 A conductor, not a 30 A one. Then 240.4(D) caps the overcurrent device at 20 A regardless of the column, and there is no next-size-up for 12 AWG copper. The 90°C figure of 30 A is the insulation rating of THHN and nothing else — a starting point for derating, never the rating of the circuit.

The gap between those columns is where most of the arguments start. "12 gauge is good for 30 amps" is true of the insulation and false of the circuit. "12 gauge is good for 20 amps" is the working answer for copper at 60°C terminations. Both statements are read off this one table.

Derating can pull even the 20 A answer down. A 12 AWG copper circuit in a 40°C attic, at 60°C terminations, is 20 × 0.82 = 16.4 A after the ambient correction — below the 20 A device protecting it, so the breaker no longer matches the conductor's corrected ampacity and the run needs 10 AWG (30 × 0.82 = 24.6 A). Start from the 75°C column instead (25 A) and the same conductor lands at 25 × 0.88 = 22 A, which holds, because the terminations are what the column depends on.

So the short answer: 20 A for 12 AWG copper, 15 A for 12 AWG aluminium, on an ordinary circuit of 100 A or less. If you need a 30 A circuit, that is 10 AWG copper (30 A at 60°C, itself capped at 30 A). The device rating you may actually use is worked through on the breaker size chart, and the run-length half of the question — where voltage drop forces a larger conductor than ampacity does — is on the voltage drop calculator.

Ambient temperature changes the answer — Table 310.15(B)(1)(1)

The base table is built on a 30°C ambient. For anything hotter or colder, multiply the table value by the correction factor for the ambient temperature and the conductor's insulation rating. Factors below 1 reduce the ampacity; a conductor in a hot attic can lose a quarter of its rating.

NEC Table 310.15(B)(1)(1) — ambient temperature correction factors, based on 30°C
Ambient (°C)Ambient (°F)60°C75°C90°C
<10<501.291.201.15
11–1551–591.221.151.12
16–2060–681.151.111.08
21–2569–771.081.051.04
26–3078–861.001.001.00
31–3587–950.910.940.96
36–4096–1040.820.880.91
41–45105–1130.710.820.87
46–50114–1220.580.750.82
51–55123–1310.410.670.76
56–60132–140—0.580.71
61–65141–149—0.470.65
66–70150–158—0.330.58

A worked case makes the size of this effect obvious. A 20 A circuit in a 40°C attic at 60°C terminations: 12 AWG copper is 20 A in the base table, and 20 × 0.82 = 16.4 A after correction — below the 20 A device protecting it. Start from the 75°C column instead (25 A) and the same conductor lands at 25 × 0.88 = 22 A, which holds. Same wire, same attic, two different answers, decided entirely by what the terminations are rated for. That is the whole reason 110.14(C) exists.

Bundled conductors — Table 310.15(C)(1)

The base table already accounts for three current-carrying conductors. Put more than three in one raceway or cable and they cannot shed heat as freely, so the allowable ampacity is reduced by the factor below. Count only conductors that carry current — a grounding conductor does not count, and neither does a neutral that is not a current-carrying conductor for the application. (How many conductors physically fit in the raceway at all is a separate check — the conduit fill chart answers that from Chapter 9.)

NEC Table 310.15(C)(1) — adjustment factors for more than three current-carrying conductors
Current-carrying conductorsPercent of table ampacity
1–3 (base table)100%
4–680%
7–970%
10–2050%
21–3045%
31–4040%
41 and above35%

Ambient correction and bundle adjustment multiply together. A feeder for 100 A at 75°C terminations normally needs 3 AWG copper (100 A). Put eight current-carrying conductors in the same conduit — four 240 V circuits, say — and the factor is 0.70: 100 × 0.70 = 70 A, too small. 1 AWG gives 130 × 0.70 = 91 A, still short; 1/0 AWG gives 150 × 0.70 = 105 A, which holds. The bundle, not the load, drove the conductor from 3 AWG to 1/0 AWG.

Worked example: is 8 AWG good for 50 amps?

This is the most common single question about this table, and the honest answer is "it depends on the column". 8 AWG copper is 40 A at 60°C, 50 A at 75°C and 55 A at 90°C.

The same logic applied to aluminium: 6 AWG aluminium is 40 A at 60°C and 50 A at 75°C, and 4 AWG aluminium is 55 A and 65 A — so the equivalent 50 A answer in aluminium is 6 AWG at 75°C or 4 AWG at 60°C.

Worked example: a 100 A feeder to a garage subpanel

Reading straight across the 75°C column, 3 AWG copper is 100 A and 1 AWG aluminium is 100 A. Those are the sizes the code permits under base conditions. Two extra checks decide whether they survive: distance (voltage drop) and bundling.

On distance, the ampacity answer is not the whole story — a 100 A load 200 ft out needs 1 AWG copper to hold a 3% drop, not 3 AWG. The distance tables and the 310.12 "83% rule" trap are worked through in the subpanel wire size guide, and the 200 A version — where the 83% rule does apply to a service — is in the 200 amp service wire size guide. The voltage drop calculator runs the arithmetic for your own run length. What this page settles is the floor: nothing smaller than 3 AWG copper or 1 AWG aluminium may be protected by a 100 A device, because 240.4(B) does not reach far enough to let 4 AWG copper (85 A) sit on a 100 A breaker.

Common mistakes with this table

Wire ampacity FAQ

What size wire do I need for 50 amps?

6 AWG copper at 60°C terminations (55 A) or 8 AWG copper if every termination in the circuit is listed for 75°C (8 AWG copper is exactly 50 A there — no headroom). In aluminium, 4 AWG at 75°C is 65 A and 3 AWG at 60°C is 65 A. The 8 AWG answer for 50 A is only valid on the 75°C column, which is why the same question gets two different answers online.

What is the ampacity of 8 gauge wire?

8 AWG copper is 40 A at 60°C, 50 A at 75°C and 55 A at 90°C in NEC Table 310.16. 8 AWG aluminium is 35 A, 40 A and 45 A in the same three columns. Those are the values for not more than three current-carrying conductors in a raceway, cable or earth at 30°C ambient — a hot attic or a bundled conduit reduces them.

Can I use the 90°C column of Table 310.16?

Not as the rating of the circuit. The 90°C column is the insulation rating of conductors such as THHN, but NEC 110.14(C) limits the ampacity you may use to the temperature rating of the lowest-rated termination, conductor or device in the circuit. For circuits of 100 A or less that is normally the 60°C column unless every device is listed for 75°C. Practically, the 90°C column is a starting point for derating calculations, not a wire size you can hand a 90°C-rated load.

What size wire for 100 amps?

At 75°C terminations, 3 AWG copper (100 A) or 1 AWG aluminium (100 A). At 60°C terminations, 1 AWG copper (110 A) or 1/0 AWG aluminium (100 A). 4 AWG copper is 85 A at 75°C, so the next standard overcurrent device it may sit on is 90 A under 240.4(B) — not 100 A. The 83% allowance in NEC 310.12 applies to a feeder carrying the entire load of a dwelling, not to a subpanel feeder, which is the single most repeated piece of bad advice on this subject.

How many amps can 12-gauge wire handle?

12 AWG copper is 20 A at 60°C, 25 A at 75°C and 30 A at 90°C in Table 310.16; 12 AWG aluminium is 15 A, 20 A and 25 A. On a normal circuit of 100 A or less the ampacity is taken from the 60°C column unless every termination is listed for 75°C, so 12 AWG copper is a 20 A conductor — and NEC 240.4(D) caps its overcurrent device at 20 A (15 A for aluminium) with no next-size-up. That is why 12 AWG copper is the standard 20 A circuit wire; the 30 A figure is the 90°C insulation rating of THHN, not a circuit rating.

Is aluminium wire legal?

Yes. Aluminium conductors are listed in the same Table 310.16 and carry roughly two sizes less current than the same size in copper — 2 AWG aluminium (90 A at 75°C) is close to 4 AWG copper (85 A). Two caveats: 14 AWG aluminium is not listed in the table at all, and aluminium terminations and connectors must be rated for aluminium, with the manufacturer's instructions followed for the connection. Most residential problems attributed to aluminium come from connections made to devices not listed for it, not from the conductor.

Related pages

Table 310.16 values, the 310.15(B)(1)(1) ambient correction factors and the 310.15(C)(1) conductor adjustment factors on this page were verified 2026-09-25 against two independent full-table reproductions — the HELUKABEL "Allowable Ampacity Tables NFPA 70: NEC 2023" document and lugsdirect.com's Table 310.16 reproduction — which agree cell for cell from 14 AWG to 2000 kcmil. The 60°C and 75°C copper and aluminium columns also match the set already published in this site's voltage drop calculator (verified 2026-09-14). Adopted code editions and local amendments vary, and none of this replaces a licensed electrician or your AHJ for work that has to pass inspection.