Conduit Fill Chart — NEC Chapter 9

How many conductors fit in a raceway, from the code's own numbers: the Chapter 9 Table 1 fill percentages, the Table 4 fill area for EMT, IMC, rigid and PVC, and the Table 5 conductor areas — with a lookup that returns the count and the space you have left.

Article 358 — Electrical Metallic Tubing
ID 0.824″ · total area 0.533 in²
Table 5 area 0.0133 in²
Nipple = 24 in. or less between enclosures
Maximum THHN/THWN-2 conductors in 3/4″ EMT16
Fill area allowed (40% of 0.533 in²)0.213 in²
12 AWG conductor area (Table 5)0.0133 in²
16 × 12 AWG = 0.213 in²39.9% of the conduit, 0.000 in² spare

Computed from Chapter 9, Tables 1, 4 and 5: fill area = total area × fill percentage, then the conductor count is that figure ÷ the Table 5 conductor area. Note 7 lets a leftover decimal of 0.8 or more round up to the next whole conductor — which is why 0.213 in² ÷ 0.0133 in² = 16.0 lands on 16, not 15. Annex C prints the same counts pre-computed; where conductor dimensions changed between code editions, the printed Annex C can differ by one at the largest sizes, and the edition your AHJ enforces governs.

How many wires fit in a conduit?

The answer is never a single number per conduit size, because it depends on the conductor size, the insulation type and how many conductors you are installing. What the code does fix is the percentage of the conduit's internal area the conductors may occupy, and then Chapter 9 gives you the two pieces of arithmetic needed to turn that into a count: the fill area of the conduit (Table 4) and the area of one conductor (Table 5).

For the most common case — three or more THHN conductors in EMT — the numbers worth memorising are small. Half-inch EMT holds nine #12s. Three-quarter-inch EMT holds sixteen. One-inch EMT holds twenty-six. Those three figures answer the great majority of "how many wires in 3/4 conduit" searches, and every one of them comes straight out of the tables on this page rather than from a rule of thumb.

The conduit fill formula, shown explicitly

The calculation in Chapter 9 is short enough to hold in your head once you have seen it written out:

Fill area = total conduit area × Table 1 percentage (40% for more than two conductors). Maximum conductors = fill area ÷ conductor area, then round the count up to the next whole number when the leftover decimal is 0.8 or more (Note 7).

The conduit's total area is the last column of Table 4 — the 100% figure. The 40%, 60%, 53% and 31% columns in the same table are already worked out for you, so you can skip the first step and divide straight out of the 40% column whenever you are installing more than two conductors. Everything on this page is computed the same way: from the total area and the percentage, never transcribed from a secondary chart.

The fill percentages — Chapter 9 Table 1

Chapter 9 Table 1 — percent of cross-sectional area
Conductors and cablesPercent of cross-sectional area
1 conductor53%
2 conductors31%
Over 2 conductors40%

The three percentages are not arbitrary. A single conductor sits near the centre of the raceway and pulls easily, so it may use more of the area; two conductors naturally align and jam more readily, so they are held to a tighter 31%; and above two, the 40% figure is the working limit. A nipple of 24 in. or less between enclosures is the one exception that may be filled to 60% (Note 4).

Table 4 — conduit and tubing fill areas

Table 4 lists, for every raceway type and trade size, the nominal internal diameter and the area at each percentage. The tables below give the 40%, 60%, 53% and 31% areas plus the total (100%) area, in square inches, for the raceways that carry most residential and light commercial work. Where a trade size is not manufactured in a given type the row is simply absent, exactly as in the code.

EMT — Article 358 — Electrical Metallic Tubing

Chapter 9 Table 4 — EMT fill area by trade size (in²)
Trade sizeMetric40% (over 2)60% (nipple)53% (1 wire)31% (2 wires)Total 100%
1/2″160.1220.1820.1610.0940.304
3/4″210.2130.3200.2820.1650.533
1″270.3460.5180.4580.2680.864
1 1/4″350.5980.8980.7930.4641.496
1 1/2″410.8141.2221.0790.6312.036
2″531.3422.0141.7791.0403.356
2 1/2″632.3433.5153.1051.8165.858
3″783.5385.3084.6882.7428.846
3 1/2″914.6186.9276.1193.57911.545
4″1035.9018.8527.8194.57314.753

IMC — Article 342 — Intermediate Metal Conduit

Chapter 9 Table 4 — IMC fill area by trade size (in²)
Trade sizeMetric40% (over 2)60% (nipple)53% (1 wire)31% (2 wires)Total 100%
1/2″160.1370.2050.1810.1060.342
3/4″210.2350.3520.3110.1820.586
1″270.3840.5750.5080.2970.959
1 1/4″350.6590.9880.8730.5111.647
1 1/2″410.8901.3351.1790.6902.225
2″531.4522.1781.9241.1253.630
2 1/2″632.0543.0812.7221.5925.135
3″783.1694.7534.1992.4567.922
3 1/2″914.2346.3505.6103.28110.584
4″1035.4528.1797.2244.22613.631

RMC — Article 344 — Rigid Metal Conduit

Chapter 9 Table 4 — RMC fill area by trade size (in²)
Trade sizeMetric40% (over 2)60% (nipple)53% (1 wire)31% (2 wires)Total 100%
1/2″160.1250.1880.1660.0970.314
3/4″210.2200.3290.2910.1700.549
1″270.3550.5320.4700.2750.887
1 1/4″350.6100.9160.8090.4731.526
1 1/2″410.8291.2431.0980.6422.071
2″531.3632.0451.8061.0563.408
2 1/2″631.9462.9202.5791.5084.866
3″783.0004.4993.9742.3257.499
3 1/2″914.0046.0065.3053.10310.010
4″1035.1537.7296.8273.99312.882
5″1298.08512.12710.7126.26620.212
6″15511.66317.49515.4549.03929.158

PVC Sch 40 — Article 352 — Rigid PVC Conduit, Schedule 40

Chapter 9 Table 4 — PVC Sch 40 fill area by trade size (in²)
Trade sizeMetric40% (over 2)60% (nipple)53% (1 wire)31% (2 wires)Total 100%
1/2″160.1140.1710.1510.0880.285
3/4″210.2030.3050.2690.1570.508
1″270.3330.4990.4410.2580.832
1 1/4″350.5810.8720.7700.4501.453
1 1/2″410.7941.1921.0530.6161.986
2″531.3161.9751.7441.0203.291
2 1/2″631.8782.8172.4881.4554.695
3″782.9074.3613.8522.2537.268
3 1/2″913.8955.8425.1613.0189.737
4″1035.0227.5326.6543.89212.554
5″1297.90411.85710.4736.12619.761
6″15511.42717.14015.1418.85628.567

PVC Sch 80 — Article 352 — Rigid PVC Conduit, Schedule 80

Chapter 9 Table 4 — PVC Sch 80 fill area by trade size (in²)
Trade sizeMetric40% (over 2)60% (nipple)53% (1 wire)31% (2 wires)Total 100%
1/2″160.0870.1300.1150.0670.217
3/4″210.1640.2450.2170.1270.409
1″270.2750.4130.3650.2130.688
1 1/4″350.4950.7420.6560.3831.237
1 1/2″410.6841.0270.9070.5301.711
2″531.1501.7241.5230.8912.874
2 1/2″631.6472.4712.1831.2774.119
3″782.5773.8653.4141.9976.442
3 1/2″913.4755.2134.6052.6938.688
4″1034.5036.7555.9673.49011.258
5″1297.14210.7139.4635.53517.855
6″15510.23915.35913.5677.93525.598

ENT — Article 362 — Electrical Nonmetallic Tubing

Chapter 9 Table 4 — ENT fill area by trade size (in²)
Trade sizeMetric40% (over 2)60% (nipple)53% (1 wire)31% (2 wires)Total 100%
1/2″160.1140.1710.1510.0880.285
3/4″210.2030.3050.2690.1570.508
1″270.3330.4990.4410.2580.832
1 1/4″350.5810.8720.7700.4501.453
1 1/2″410.7941.1921.0530.6161.986
2″531.3161.9751.7441.0203.291

FMC — Article 348 — Flexible Metal Conduit

Chapter 9 Table 4 — FMC fill area by trade size (in²)
Trade sizeMetric40% (over 2)60% (nipple)53% (1 wire)31% (2 wires)Total 100%
3/8″120.0460.0700.0610.0360.116
1/2″160.1270.1900.1680.0980.317
3/4″210.2130.3200.2820.1650.533
1″270.3270.4900.4330.2530.817
1 1/4″350.5110.7660.6770.3961.277
1 1/2″410.7431.1150.9850.5761.858
2″531.3071.9611.7331.0133.269
2 1/2″631.9632.9452.6021.5224.909
3″782.8274.2413.7472.1917.069
3 1/2″913.8485.7735.0992.9839.621
4″1035.0277.5406.6603.89512.566

LFMC — Article 350 — Liquidtight Flexible Metal Conduit

Chapter 9 Table 4 — LFMC fill area by trade size (in²)
Trade sizeMetric40% (over 2)60% (nipple)53% (1 wire)31% (2 wires)Total 100%
3/8″120.0770.1150.1020.0600.192
1/2″160.1250.1880.1660.0970.314
3/4″210.2160.3250.2870.1680.541
1″270.3490.5240.4630.2710.873
1 1/4″350.6110.9170.8100.4741.528
1 1/2″410.7921.1891.0500.6141.981
2″531.2981.9481.7201.0063.246
2 1/2″631.9532.9292.5871.5134.881
3″782.9904.4853.9622.3177.475
3 1/2″913.8935.8395.1573.0179.731
4″1035.0777.6156.7273.93512.692

Table 5 — conductor areas for the wire you actually pull

The conductor side of the calculation depends on the insulation. THHN, THWN and THWN-2 are the types installed in raceway almost all of the time, and Table 5 gives their approximate area by size. Other insulations are larger — RHH, RHW and RHW-2, for instance, have areas roughly twice those of THHN at the same gauge, and XHHW has its own column in Table 5A. If you are pulling one of those, use its actual dimensions rather than the THHN figures below.

Chapter 9 Table 5 — approximate area of THHN / THWN / THWN-2 conductors
Conductor sizeArea (in²)Area (mm²)
14 AWG0.00976.258
12 AWG0.01338.581
10 AWG0.021113.61
8 AWG0.036623.61
6 AWG0.050732.71
4 AWG0.082453.16
3 AWG0.097362.77
2 AWG0.115874.71
1 AWG0.1562100.8
1/0 AWG0.1855119.7
2/0 AWG0.2223143.4
3/0 AWG0.2679172.8
4/0 AWG0.3237208.8
250 kcmil0.3970256.1
300 kcmil0.4608297.3
350 kcmil0.5242338.2
400 kcmil0.5863378.3
500 kcmil0.7073456.3
600 kcmil0.8676559.7
700 kcmil0.9887637.9
750 kcmil1.0496677.2
800 kcmil1.1085715.2
900 kcmil1.2311794.3
1000 kcmil1.3478869.5

Quick counts — THHN in EMT, ready to read

The single table below answers the questions people actually type, without any division: the maximum number of THHN conductors in each EMT trade size, for the six conductor sizes used in branch circuits. The numbers are computed from the two tables above using Note 7, not copied from a manufacturer flyer.

Maximum THHN / THWN-2 conductors in EMT, 40% fill (computed from Tables 1, 4 and 5)
EMT trade size#14#12#10#8#6#4
1/2″1295321
3/4″221610642
1″352616974
1 1/4″61452816127
1 1/2″846138221610
2″13810163362616
2 1/2″241176111644628
3″364266167966943
3 1/2″4763472191269156
4″60844327916111671

Worked example — checking three-quarters EMT by hand

You are pulling #12 THHN for a lighting circuit and want to know the largest conduit a single run will take at the 40% limit.

Common mistakes with conduit fill

Conduit fill FAQ

How many #12 wires fit in 3/4 inch EMT?

Sixteen. Table 4 gives 3/4 EMT a 40% fill area of 0.213 in², and Table 5 gives a #12 THHN/THWN-2 conductor an area of 0.0133 in². 0.213 ÷ 0.0133 = 16.0, so sixteen conductors fill the raceway to just over 40% — the maximum the code allows for more than two conductors. This is the single most-searched conduit fill question, and 16 is the number to remember.

How many #12 wires fit in 1/2 inch EMT?

Nine. 1/2 EMT has a 40% fill area of 0.122 in². Dividing by the 0.0133 in² area of a #12 THHN leaves 9.17, which is 9 conductors — the decimal is below 0.8, so Note 7 does not round it up. Swap to #14 and the same half-inch conduit holds 12.

Why is the conduit fill limit 40 percent?

Chapter 9 Table 1 sets the percentage of the conduit's internal cross-sectional area that conductors may occupy: 53% for a single conductor, 31% for exactly two, and 40% for more than two. The limits exist so the conductors can be pulled without damaging the insulation, and so heat can dissipate. The 40% figure for three or more conductors is the one almost every real installation uses.

Do equipment grounding conductors count toward conduit fill?

Yes. Note 3 under Chapter 9 Table 1 states that equipment grounding or bonding conductors, where installed, must be included in the fill calculation, using their actual dimensions whether insulated or bare. Forgetting the ground is one of the two most common fill errors — the other is forgetting that a cable with an overall jacket counts as a single conductor (Note 9).

What is the 60 percent nipple rule?

Note 4 permits a nipple — a length of conduit or tubing no longer than 600 mm (24 in.) installed between boxes, cabinets or similar enclosures — to be filled to 60% of its total cross-sectional area. The same note says the 310.15 adjustment factors need not apply to that condition. The 60% allowance applies only to a nipple, not to a general run.

Does conduit fill affect how much current a wire can carry?

Yes, and the two rules are separate. Fill is about how many conductors physically fit; the ampacity adjustment under 310.15(C)(1) reduces how much current each one may carry once you install more than three current-carrying conductors in a raceway — 80% for four to six, 70% for seven to nine, and down from there. A conduit that passes the fill check can still force a larger wire because of the derating.

Where these numbers came from

Chapter 9 Tables 1, 4 and 5 were read on 2026-10-02 from the NFPA-licensed single-user copy of the NEC Chapter 9 Tables PDF and cross-checked two ways: against the Western Tube conduit-wire fill chart (itself referenced from Annex C of an earlier edition) and against the NECA/IBEW Annex C Table C.1 reproduction, which agree on every small-conductor cell on this page. The Tables 4 areas and the Table 5 THHN areas have been stable for decades, but the code is adopted and reissued, so the page states the method rather than a single printed count. Confirm the figures against the edition your authority having jurisdiction enforces.

This is a working reference, not engineering. Fill is a starting check: it tells you how many conductors physically fit, not whether the circuit is correctly sized. Conductor ampacity, the 310.15 adjustment factors, box fill and the termination temperature rules all apply on top of it.