Breaker Size Chart — NEC 240.6(A), 240.4(D) and 210.20

The standard overcurrent device ratings, the caps that override them on small conductors, the 125% rule for continuous loads, and the breaker and wire for the appliances people actually ask about — water heaters, dryers, ranges, air conditioners and mini-splits.

Nameplate rating, or the calculated load
Watts are divided by the voltage below
120 for a 120 V circuit, 240 for a range, dryer or water heater
Water heaters, EV chargers and lighting are continuous
Aluminium is not listed for 14 AWG
The same rule as the ampacity chart — the weakest termination wins
Load current (before the 125% rule)18.75 A
Minimum device rating — load × 125%, 210.20(A)23.44 A
Standard breaker size to use (240.6(A))25 A
Minimum conductor — 10 AWG Cu30 A at 60°C
Conductor ampacity vs device5 A spare on a 25 A device
Upper limit, single appliance (422.11(E)(3))30 A — 150% of 18.75 A

The device rating and the conductor size are two separate answers that have to agree. This lookup returns the minimum legal device under 210.20(A) and the conductor that may sit on it. A single non-motor-operated appliance such as a water heater may legally use a larger device, up to 150% of its rated current — that is why the same water heater gets both "25 A" and "30 A" answers online, and both are right. Ampacities are NEC Table 310.16, the 240.4(D) caps are applied as a hard ceiling, and 240.4(B) is applied explicitly. No ambient or conductor-count derating is applied here — do that first on the ampacity chart if the circuit runs hot or bundled.

The breaker and the wire are two separate answers

Almost every breaker question online is really two questions wearing one hat. What device protects this circuit, and what conductor may sit behind it? The NEC answers them in different articles, with different arithmetic, and a circuit only passes inspection when both answers agree.

The device rating comes from Article 210 and Article 240: you size the overcurrent device to the load, then you check that the conductor can carry it. The conductor ampacity comes from Table 310.16, which is a thermal limit and nothing to do with the breaker except that the two numbers have to be compatible. A 30 A breaker on 14 AWG copper is wrong even though a 30 A breaker is a perfectly standard device, and 14 AWG copper is a perfectly normal conductor — they are simply not allowed to be paired. NEC 240.4(D) is the section that says so.

Size the load first, not the wire. Work out the current, apply 125% if the load is continuous, round up to a standard device rating — then find the conductor that may legally carry that device. Doing it in the other order is how people end up trying to protect 14 AWG at 20 A because the wire was already in the wall.

Standard breaker and fuse sizes — NEC Table 240.6(A)

The device you round up to has to be a standard rating. Table 240.6(A) lists them; nonstandard ratings exist and are permitted, but the next-size-up rule in 240.4(B) only reaches a standard rating, so the list is the list you actually shop from.

NEC Table 240.6(A) — standard ampere ratings for fuses and inverse-time circuit breakers
Standard ratings (A) — fuses and breakers
15 · 20 · 25 · 30 · 35 · 40 · 45 · 50 · 60 · 70 · 80 · 90 · 100 · 110 · 125 · 150 · 175 · 200 · 225 · 250 · 300 · 350 · 400 · 450 · 500 · 600 · 700 · 800 · 1000 · 1200 · 1600 · 2000 · 2500 · 3000 · 4000 · 5000 · 6000

Those are the sizes that exist as both fuses and inverse-time circuit breakers. Five more ratings are standard for fuses only — 1, 3, 6, 10, 601 amperes — where 1 A through 10 A are the small control and instrument sizes and 601 A is the odd one out. There is no standard 6 A residential circuit breaker, which matters when a load calculation comes out at 5 A and someone reaches for the nearest number.

240.4(D) — the caps that override everything above

Five conductor sizes are capped regardless of what the ampacity table says. The cap is on the overcurrent device, it applies after any ambient or conductor-count correction factors, and unlike the general next-size-up rule it has no round-up allowance at all.

NEC 240.4(D) — maximum overcurrent protection for the small conductors
ConductorMax device — copperMax device — aluminium
14 AWG15 Anot listed A
12 AWG20 A15 A
10 AWG30 A25 A

The practical effect is that 14 AWG copper is a 15 A conductor and no amount of 75°C or 90°C column reading changes that. 12 AWG copper is a 20 A conductor, which is why the standard residential 20 A circuit — kitchen counters, laundry, bathroom — uses it. And 10 AWG copper is a 30 A conductor, which is why a 30 A dryer or water heater circuit is wired in 10 AWG.

The 125% rule — NEC 210.20(A)

A continuous load is one expected to run for three hours or more. For those, the overcurrent device may not be smaller than the noncontinuous load plus 125% of the continuous load. The maths is trivial and the consequences are not: 125% is a 25% oversizing of the device, which is exactly what turns an 18.75 A water heater into a 23.4 A requirement and therefore a 25 A breaker.

The 125% is not padding and it is not a manufacturer's preference. A breaker holds its rating in a specific ambient environment; a device run at exactly its rating for hours drifts toward its thermal trip. The code buys the difference in the device rating rather than hoping the enclosure stays cool.

What the rule does not say is that every appliance counts as continuous. A range, a dryer and a well pump cycle on and off, and are treated as noncontinuous for this purpose. Water heaters, EV chargers and most lighting are the continuous ones — which is why a 4,500 W water heater gets a 25 A minimum while a 4,500 W dryer element would not.

240.4(B) — when a breaker may be bigger than the wire

Because devices only come in standard sizes and ampacities do not, there are cases where a conductor's ampacity falls between two standard device ratings. 240.4(B) permits the next standard size up, provided three conditions hold: the conductors are not part of a branch circuit supplying more than one receptacle for cord-and-plug portable loads; the ampacity does not itself correspond to a standard rating; and the next size selected does not exceed 800 A.

A worked case shows how narrow the permission is. 8 AWG copper is 40 A at 60°C, and 40 A is not a device whose next standard rating is 50 A — it is 45 A. So 240.4(B) does not let 8 AWG copper sit on a 50 A breaker at 60°C terminations, and the correct answer is 6 AWG copper (55 A). Put the same conductor on a 45 A breaker and the round-up does apply, because 45 A is the very next standard rating above 40 A. The same conductor, the same table cell, two different answers decided entirely by which device you are trying to fit.

422.11(E)(3) — why the same water heater has two right answers

210.20(A) sets the floor for the device. For a single non-motor-operated appliance, 422.11(E)(3) sets a ceiling: the branch circuit overcurrent protection may not exceed 150% of the appliance rated current, rounded up to the next standard rating if 150% does not land on one. For a 4,500 W, 240 V heater that ceiling is 28.1 A, so a 30 A device is legal as well as a 25 A one.

That is the whole explanation for the argument you will find in every forum thread on the subject. One electrician says 25 A because that is the 210.20(A) minimum; another says 30 A because that is the common field answer and 422.11(E)(3) permits it. Both are quoting the code correctly and quoting different sections of it. The lookup on this page shows you both numbers, so you can see the range rather than one end of it.

Worked example — the 4,500 W water heater, step by step

That is the entire calculation, and it is worth doing by hand once because it is the same five steps for a dryer, a range, a hot tub or an EV charger.

Worked example — a 40 A EV charger

An EV charger is treated as a continuous load, so 625.41 requires the branch circuit overcurrent device to be sized at not less than 125% of the maximum load. A charger rated 40 A therefore needs at least 50 A of device, and 50 A is already a standard rating — no rounding needed. The conductor is the one that may carry a 50 A device: 6 AWG copper at 60°C (55 A), or 8 AWG copper if every termination is listed for 75°C, where 8 AWG is exactly 50 A. Most installers take 6 AWG, because a 100 ft run to a garage usually fails voltage drop before it fails ampacity — that part of the job belongs to the voltage drop calculator.

Breaker and wire for common appliances

The rows below are the circuits a residential electrician sizes every week. The device column is the code answer for the situation in the first column, and the basis column names the section it comes from — so when a number disagrees with something you read elsewhere, you can check which section each of you is quoting.

Typical branch circuits for household appliances, with the NEC section behind each one
Circuit / applianceBreakerConductor (copper)Code basis
Lighting and general-use receptacles15 A14 AWG Cu240.4(D) caps 14 AWG Cu at 15 A; 210.19(A)(4) sets 14 AWG as the smallest branch-circuit conductor.
Kitchen countertop, laundry and bathroom receptacles20 A12 AWG Cu210.11(C) requires the 20 A small-appliance, laundry and bathroom branch circuits in a dwelling; 240.4(D) caps 12 AWG Cu at 20 A.
Electric water heater (4,500 W @ 240 V = 18.75 A)25 A minimum, 30 A typical10 AWG Cu210.20(A) requires at least 125% of a continuous load (18.75 × 1.25 = 23.4 A → 25 A device). 422.11(E)(3) allows up to 150% of the appliance rating for a single non-motor appliance (18.75 × 1.5 = 28.1 A → 30 A device), which is why the field answer is 30 A.
Household electric clothes dryer (240 V)30 A10 AWG Cu220.54 sets the dryer demand load at 5,000 W or the nameplate, whichever is larger; 110.3(B) requires the branch circuit to match the rating marked on the appliance, and the standard dryer receptacle is the 30 A NEMA 14-30. 250.140 governs bonding the frame.
Household electric range or oven (over 8¾ kW)40 A minimum, 50 A typical40 A → 8 AWG Cu · 50 A → 6 AWG Cu210.19(A)(3): over 8¾ kW the minimum branch circuit is 40 A. 210.23(C) permits 40 A and 50 A branch circuits to supply cooking appliances, and Table 220.55 lets the calculated load be less than the sum of the nameplates.
Central air conditioner or heat pumpthe MOP printed on the nameplateper the nameplate MCA440.22(A) caps short-circuit and ground-fault protection at 175% of the compressor rated-load current (225% if that will not start the motor), and 440.4(B) says the device may not exceed the rating marked on the nameplate. The nameplate value already is the code answer.
Ductless mini-split (single-zone)the MOCP printed on the nameplate (15–30 A typical)per the nameplate MCASame Article 440 method as a central unit. A 20 A breaker on a circuit whose nameplate says MOCP 20 A is correct even when the MCA is only 12 A — the device protects the equipment, not the load.
EV charger (EVSE)125% of the EVSE rated current40 A EVSE → 50 A circuit → 6 AWG Cu625.41 requires the branch-circuit overcurrent device to be sized at not less than 125% of the maximum load, because EV charging is treated as a continuous load. 625.42 sets the equipment rating basis.

Two of those rows deserve a warning attached. The first is HVAC: Article 440 deliberately permits a device larger than the conductor ampacity, because the breaker there is providing short-circuit and ground-fault protection only — the equipment's own overload protection is inside the unit. A 40 A breaker on a circuit with a 28 A minimum circuit ampacity is not a mistake; it is what the nameplate asks for. Never "correct" an HVAC circuit down to the conductor ampacity.

The second is the range and dryer rows, where the receptacle standard and the code meet. A new dryer circuit is four-wire on a NEMA 14-30, and a new range circuit is four-wire on a NEMA 14-50; the three-wire allowance in 250.140 is for existing installations only. Running a new three-wire circuit and bonding the appliance frame to the neutral is the single most common error in this part of the trade, and no inspector will pass it.

Wire size by breaker rating — and the ground that goes with it

"What size wire for a 30 amp breaker" and its 50 A and 60 A siblings are the most-asked conductor questions in the trade, and the honest answer needs three numbers, not one: the conductor by the termination column you are actually using, the same conductor in aluminium if you are running aluminium, and the equipment grounding conductor, which is sized from the breaker and not from the current carrying conductors.

Conductor and equipment grounding conductor for common breaker ratings — NEC Table 310.16 (60 °C / 75 °C columns) and Table 250.122 (EGC)
BreakerCu @ 60 °CCu @ 75 °CAl @ 60 °CAl @ 75 °CEGC (250.122)
15 A14 AWG (15 A)14 AWG (20 A)12 AWG (15 A)12 AWG (20 A)14 Cu / 12 Al
20 A12 AWG (20 A)12 AWG (25 A)10 AWG (25 A)10 AWG (30 A)12 Cu / 10 Al
30 A10 AWG (30 A)10 AWG (35 A)8 AWG (35 A)8 AWG (40 A)10 Cu / 8 Al
40 A8 AWG (40 A)8 AWG (50 A)6 AWG (40 A)8 AWG (40 A)10 Cu / 8 Al
50 A6 AWG (55 A)8 AWG (50 A)4 AWG (55 A)6 AWG (50 A)10 Cu / 8 Al
60 A4 AWG (70 A)6 AWG (65 A)4 AWG (55 A)4 AWG (65 A)10 Cu / 8 Al

Read the table as: pick the column your terminations are listed for, then take the conductor. The 60 °C column is the default for circuits of 100 A or less unless the breaker, lugs, receptacles and connectors are all listed for 75 °C — that is 110.14(C)(1), and it is why the internet "disagrees" about these answers. A 60 A circuit takes 4 AWG copper at 60 °C (70 A) but only 6 AWG copper at 75 °C (65 A), while a 50 A circuit is 6 AWG at 60 °C (55 A) and 8 AWG — exactly 50 A, no headroom — at 75 °C. When in doubt, take the 60 °C column. It is never wrong, only occasionally larger than necessary.

The EGC column comes from a completely different table. NEC 250.122 sizes the equipment grounding conductor from the rating of the overcurrent device, not from the ungrounded conductors, so every breaker from 30 A through 60 A asks for the same 10 AWG copper ground (8 AWG aluminium). A 15 A circuit takes 14 AWG Cu and a 20 A circuit takes 12 AWG Cu. The catch is 250.122(B): if you increase the ungrounded conductors for any reason — the classic one being a long feeder upsized for voltage drop — the EGC has to be increased in the same proportion. That is the step people miss on a 200 ft garage feed, and it is the reason a voltage drop calculation changes the ground wire, not just the hots.

240.4(D) still caps the low end. The table shows 10 AWG copper carrying a 30 A breaker — legal, and exactly at the 30 A cap with no room to round up. The aluminium answer for 30 A is 8 AWG, because 10 AWG aluminium is capped at 25 A and the cap has no next-size-up allowance. This is the same rule already printed in the 240.4(D) table above, and it is the one that decides 30 A circuits in aluminium.

One worked line to check by hand: a 60 A breaker feeding a subpanel, 75 °C terminations. Table 310.16 gives 6 AWG copper = 65 A in the 75 °C column, which covers 60 A with 5 A spare. The EGC from Table 250.122 is 10 AWG copper. If the run is long enough that voltage drop forces the hots up to 4 AWG, 250.122(B) scales the ground up with them, so the 10 AWG answer stops being correct. The subpanel wire size guide works that exact arithmetic end to end.

How many outlets can you put on one circuit?

There is no single number, because the code answers two different questions. For a commercial or non-dwelling branch circuit, NEC 220.14(I) counts a receptacle outlet at 180 volt-amperes per yoke — a duplex counts once, because it is one yoke — so the maximum is a matter of division. For a dwelling, the same 180 VA rule does not apply at all: 220.14(J) sends the receptacle load to 220.41 and Table 220.42, calculated at 3 VA per square foot, and sets no yoke limit on a general-use circuit. Almost every page on the internet quotes the commercial number and then tells a homeowner it is a limit. It is not.

Maximum receptacle yokes per circuit by the NEC 220.14(I) 180 VA method (non-dwelling), with the 80% continuous-load cap applied
CircuitLoad availableMax yokes (180 VA each)With 80% continuous cap
15 A / 120 V1,800 VA108
20 A / 120 V2,400 VA1310

The arithmetic is the whole trick. A 20 A / 120 V circuit has 20 × 120 = 2,400 VA available; each yoke is 180 VA; 2,400 ÷ 180 = 13.33, and because you cannot install two-thirds of an outlet the answer is 13. That single division is where the well-worn "13 outlets on a 20 amp circuit" rule comes from. A 15 A circuit gives 15 × 120 = 1,800 VA ÷ 180 = exactly 10. A quick sanity check: 13 yokes × 180 VA = 2,340 VA, which is under the 2,400 VA line; a 14th would push it to 2,520 VA and fail.

Two refinements matter. First, the figure assumes the circuit is not carrying a continuous load. General branch circuits should not carry more than 80% continuously (the 125% rule in 210.19(A) and 210.20(A), applied above), so a 20 A circuit loaded continuously works out at 16 A × 120 V = 1,920 VA ÷ 180 = 10 yokes, and a 15 A circuit at 12 A × 120 V = 1,440 VA ÷ 180 = 8 yokes. Second, in a dwelling none of it applies: a 2,500 ft² house computes its receptacle load at 2,500 × 3 VA = 7,500 VA, which is 62.5 A spread across as many general-use circuits as the designer chooses — roughly 55 small-load receptacles if you assume 180 VA, split over about four 15 A circuits. That is a design split, not a code cap.

Where the dwelling rules do bite is in the required circuits. NEC 210.11(C)(1) demands two 20 A small-appliance branch circuits for the kitchen, dining and pantry receptacles, and 210.11(C)(2) demands one 20 A laundry circuit. Those circuits come with their own appliance-load arithmetic (Table 220.52) and are separate from the general-use calculation. The appliance rows above name the section behind each one.

Common mistakes with breaker sizing

Breaker size FAQ

What size breaker do I need?

Multiply a continuous load by 125%, add any noncontinuous load, then round up to the next standard rating in Table 240.6(A). A 18.75 A water heater that runs continuously needs at least 23.4 A of device, so the answer is a 25 A breaker — the next standard size up. NEC 210.20(A) is the rule and 240.6(A) is the list of sizes you are allowed to round up to.

What size breaker for a water heater?

A 4,500 W, 240 V element draws 18.75 A. NEC 210.20(A) sets the minimum device at 125% of that, 23.4 A, which is a 25 A breaker. But 422.11(E)(3) lets a single non-motor-operated appliance be protected up to 150% of its rating, 28.1 A, which rounds up to a standard 30 A breaker — and 30 A on 10 AWG copper is what you see in the field. Both are code-correct; the 30 A device gives the element more room before a nuisance trip on a cold start.

What size breaker for an electric dryer?

A household electric dryer is a 30 A circuit on 10 AWG copper with a NEMA 14-30 receptacle. NEC 220.54 sets the dryer demand load at 5,000 W or the nameplate, whichever is larger, and 110.3(B) requires the branch circuit to match what the appliance is marked for. 250.140 governs bonding the dryer frame, and a new circuit must be four-wire — the three-wire allowance is only for existing installations.

What size breaker for a range or oven?

A household electric range over 8¾ kW needs a minimum 40 A branch circuit (210.19(A)(3)), and 210.23(C) permits 40 A and 50 A circuits for cooking appliances. Most modern ranges are wired for a 50 A NEMA 14-50 receptacle on 6 AWG copper; a 40 A circuit on 8 AWG is the smaller option. The nameplate kW decides which one you need.

What size breaker for an air conditioner or mini-split?

Whatever the nameplate says. Air-conditioning and refrigeration equipment is covered by Article 440, not by the normal conductor rules: 440.22(A) caps short-circuit and ground-fault protection at 175% of the compressor rated-load current (225% if that will not start the motor), and 440.4(B) says the device may not exceed the rating marked on the nameplate. The MOCP (maximum overcurrent protection) on the label already is the code answer, so a 20 A breaker on a unit marked MOCP 20 A is correct even when the minimum circuit ampacity is only 12 A.

Can I put a 20 A breaker on 14 gauge wire?

No. NEC 240.4(D) caps 14 AWG copper at 15 A of overcurrent protection, 12 AWG copper at 20 A, 10 AWG copper at 30 A, and 12 and 10 AWG aluminium at 15 A and 25 A. There is no next-size-up allowance for those sizes, and the cap applies after any ambient-temperature or conductor-count correction factors have been applied.

Does a 50 A breaker always need 6 gauge wire?

Only at 60°C terminations, where 6 AWG copper is 55 A. If every termination in the circuit — breaker, lugs, receptacle, connectors — is listed for 75°C, 8 AWG copper is exactly 50 A and may be used, though with zero headroom. NEC 110.14(C) is what decides the column, and for circuits of 100 A or less the default is 60°C unless the equipment is listed for 75°C.

How many outlets can I put on a 20 amp circuit?

In a non-dwelling occupancy, NEC 220.14(I) counts each receptacle yoke at 180 volt-amperes, so a 20 A / 120 V circuit works out at 20 × 120 = 2,400 VA ÷ 180 VA = 13.3, which is 13 duplex outlets. That is a load-calculation figure, not a device count, and if the circuit carries a continuous load you must apply the 80% rule first, which brings it down to 10. In a dwelling there is no yoke limit at all: 220.14(J) sends the receptacle load to 220.41 and Table 220.42, calculated at 3 VA per square foot, so a house circuit can carry far more than 13 — the practical ceiling is voltage drop and nuisance trips, not a code number.

What size ground wire for a 60 amp breaker?

NEC Table 250.122 sizes the equipment grounding conductor from the rating of the circuit overcurrent device, not the conductors. For any device not exceeding 60 A the minimum EGC is 10 AWG copper or 8 AWG aluminium, so a 60 A breaker needs a 10 AWG copper ground. One catch: 250.122(B) says that if you increase the ungrounded conductors in size — for example upsizing a long run for voltage drop — the EGC has to be increased proportionally too. On a long feeder, do not leave the ground at its table minimum.

Where these numbers came from

Table 240.6(A) was verified 2026-09-26 against the NEC text reproduced at electricallicenserenewal.com, in both its 2014 paragraph form and its 2017 table form, including the five additional fuse-only ratings. The 240.4(B) text quoted above, including the three conditions and the 2023 sentence on adjustable-trip devices, comes from the same source. The 240.4(D) caps were verified 2026-09-14 and are already used by the ampacity chart and the voltage drop calculator. The appliance rows are assembled from the sections named in each row — 210.19(A)(3), 210.23(C), 220.54, 220.55, 250.140, 422.11(E)(3), 440.22(A), 440.4(B) and 625.41 — cross-checked on 2026-09-26 against EC&M and IAEI commentary on Article 210 and Mike Holt material on Articles 422 and 440. The breaker-to-conductor and EGC rows were assembled from the Table 310.16 set verified 2026-09-25 and NEC Table 250.122, verified 2026-10-15 against the TEP engineering standard PDF (docs.tep.com/doc/ESR/SR-453.pdf), extracted twice, and cross-checked against eepower and turn2engineering reproductions of the table. The 180 VA outlet arithmetic follows NEC 220.14(I) with the dwelling exception in 220.14(J)/220.41, verified 2026-10-13 and re-confirmed 2026-10-16. Local amendments and the authority having jurisdiction always win.